Vortex flow meters
measure steam in three ways:
 
The first, and the most widely used, is the vortex flowmeter with temperature and pressure compensation. This is an indirect vortex mass flowmeter. In actual use, the density is indirectly measured through
the measurement of temperature and pressure, and then multiplied by the volume measured by the vortex flowmeter to calculate the mass.
 
Second, the lift-type vortex flowmeter directly measures the quality of the medium. The theoretical basis is: the mass flow of the medium has a certain proportional relationship with the strength of the vortex,
and the mass of the medium can be directly calculated by calculating the strength of the vortex.
 
The last one is the differential pressure vortex mass flow meter, differential pressure signal + vortex flowmeter = differential pressure vortex mass flowmeter. The differential pressure signal is the pressure
difference between the two pressure taking holes at specific positions upstream and downstream of the generating body. The axes of the two pressure taking holes should be in the same plane as the axis
of the generating body. The distance of the pressure taking hole has a significant influence on the size and stability of the differential pressure value. The distance is short, the differential pressure pressure
signal is large, but the stability is poor; the distance is long, the opposite is true. It is very important to choose the appropriate pressure-tapping hole location through experimentation. Compared with the
lift-type vortex mass flowmeter, this instrument is simpler and easier to implement.








If you want to know more detailed parameters, quotation and installation of steam vortex flowmeter, please contact winny:sales01@cxflowmeter.com



 

Last:Audio dispensing flow meter epo.. Next:CIXI spray flow meter is used f..

Contact Us

Office Address: Room 402, No. 650, Xinzhuan Rd., Jiuting Town, Songjiang District, Shanghai, China (Mainland)

Phone:021-57635022

E-mail:info@gnflowmeter.com

E-mail:sales@gninstruments.com

關(guān)閉
精品视频无码一区二区三区,亚洲精品中文无码AV在线播放,蜜臀av无码精品人妻色欲,青娱乐国产盛宴免费青娱乐,久久久久精品午夜理论片欧美